username:
password:
Sign In
How To Register

The Pig Blind: Current Settings


Sensata support of these products ends Dec 31, 2025.
Settings Date: 2025-07-16 15:28:03
Report received 6 seconds ago.
Inverter Settings
Model: MS4024PAE
Revision: 6.1
Stack Mode: Standalone Unit
Remote Settings
Revision: 4.0
AC Search: No Searching, Always On
AC Shore Amps: 30
Low VAC Dropout: 60 VAC
Charge Rate: 80% of full value
Auto Generator Start: Enabled
Battery Size:460 amp/hours
Low Battery Cut-Out: 23.6 VDC
Absorb Voltage: 28.8 VDC
Float Voltage: 26.4 VDC
Equalize Voltage: 28.8 VDC
Automatic Generator Start Settings
(controlled by ME-ARC)
AGS Revision: 6.1
Start Generator When:
Battery Voltage:@ 24.4 volts for [1m 0s], run to 28.8 volts for [1m 0s]
Generator Settings:
Warm Up Time:[2m 0s]
Cool Down Time:[2m 0s]
Max Run Time:[6h 0m]
Generator Exercise:Every 30 days at 08:00 for [12m].
Battery Monitor
Revision: 1.3
Battery Efficiency: 99%
Battery Size:460 amp/hours
MagWeb
Firmware Date: 2011-06-13


Sensata support of these products ends Dec 31, 2025.